The HXGN-12 switchgear is suitable for distribution systems in industrial and mining enterprises, residential communities, high-rise buildings, and school parks. It serves as an indoor three-phase AC power supply unit and terminal distribution equipment for 12kV, 50Hz ring network applications. It can switch on or off the rated load current and the no-load current of transformers, as well as disconnect or connect overhead lines, cable lines, or capacitive currents over a certain distance. The load switch-fuse combination cabinet can interrupt the rated short-circuit current in a single operation.

Introduction of High and Low Voltage Switchgear HXGN-12

Some structural features of High and Low Voltage Switchgear HXGN-12:

The HXGN-12 High and Low Voltage Switchgear is constructed from 8MF type steel, which is partially welded and then bolted together. It primarily houses the FZN21-12 type two-position vacuum load switch, which is used in conjunction with a fuse equipped with an impactor to form a combined electrical device. This type of switchgear can be flexibly equipped with current transformers (CT), potential transformers (PT), and ZnO surge arresters. Its base is fitted with a removable access cover for easy cable entry, and for overhead cable entry, a busbar channel can be added according to user requirements.

Technical Specification of High and Low Voltage Switchgear HXGN-12

No.ItemUnitData
1Rated VoltageKV7.2/12
2Main Busbar Rated CurrentA400;630;1250
3Rated CurrentIncoming CabinetA400;630;1250
Outlet CabinetA125
4Rated Short time Withstand CurrentKA20
5Rated Peak Withstand CurrentKA31.5
6Rated Short Circuit Closing Current Peak ValueKA50
7Rated Active Load Breaking CurrentA630
8Rated Closed Loop Breaking CurrentA630
9Rated Cable Charging CurrentA10
10Ground Switch Rated Short Time Withstand CurrentKA20
11Ground Switch Rated Peak Withstand CurrentKA50
12Ground Switch Rated Short Circuit Closing Current Peak valueKA50
13Rated AC Current of Combination ApparatusA3150
141min Power Frequency Withstand VoltageInterphase Relative Vacuum FractureKV42
Isolating Distance48
15Lightning Impulse Withstand VoltageInterphase Relative Vacuum FractureKV75
Isolating Distance85
16Mechanical LifeVacuum Load Switchtime10000
Isolation Knife Grounding Knife2000
17Load SwitchAverage Closing Speedm/S0.6±0.2
Average Opening Speedm/S1.1±0.2
Three-phase Different PhasesmS≤2
18Fuse for Combined AppliancesMaximum Rated CurrentA125
Rated Short Circuit Breaking CurrentKA31.5
19IP CodeIP2X